4–20 mA Loop Calculator
Check available loop voltage and transmitter headroom. Fast, browser-local and free to use.
A 4–20 mA loop needs enough voltage for the transmitter after the PLC input, cable, and any barrier have taken their voltage drop. This check uses the worst case: 20 mA.
PLC burden: find this in the analog-input datasheet; 250 Ω is common for a 1–5 V input.
Cable resistance: include both wires. At 20 mA, every 100 Ω causes a 2 V drop.
Total loop burden
270 Ω
PLC + barrier + cable
Voltage drop at 20 mA
5.4 V
Burden × 0.020 A
Voltage at transmitter
18.6 V
Supply − loop drop
Voltage headroom
6.6 V
Available − transmitter minimum
Loop status
OPERATES
Transmitter has enough operating voltage.
The loop has 6.6 V spare voltage at 20 mA.